EasyManua.ls Logo

TBB APOLLO MAXX Series - Parameter Configuration: Output and ACin; Output Parameters; AC Input Parameters

TBB APOLLO MAXX Series
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Apollo Maxx User Manual
19
01
Output frequency
50~60Hz
Step:10Hz
Default:50Hz
(only in standby mode)
02
Parallel mode
0-Stand-alone
1-Parallel
2-Three-Phase
Default:0
(only in standby mode)
03
Parallel phase
1-Phase-U (L1)
2-Phase-V (L2)
3-Phase-W (L3)
Default:1
(only in standby mode and
parallel system)
04
Synchronize parallel parameters
1 (Press <ENTER> to trigger
the effect once)
Default:0
05
Fault unlock
1 (Press <ENTER> to trigger
the effect once)
Default:0
06
Fan dedusting
1 (Press <ENTER> to trigger
the effect once)
Default:0
07
Parallel address
1~MaxU: 3 / V: 2 / W: 2
Default:1
08
Independent mode selection
at battery bank of parallel
system
0-Disable
1-Enable
Default:0
ACin Parameter
10
AC in source selection
0-Grid
1-Generator
Default:0
(only in standby mode)
11
Power assist current
0~Max(Rate AC input Current)
Step:1A
Default: Max
12
AC in source priority
0-AC First
1-BATT First
2-Time Ctrl
3-Ubat Ctrl/ SOC Ctrl
4-AC IN backup
Default:0