Air Conditioner Service Manual 
 
40 
 
 
3) Check the system pressure, recharge refrigerant if the pressure is low, and discharge some    
refrigerant  if the pressure is too high. 
4) Check the outdoor ventilation and if there is any obstruction that affects the normal radiating of the air 
conditioner, and installation again. 
5) If the above inspections are normal, but the fault remains unsolved, please replace the outdoor PCB. 
Re-energize and check the protection code on display. Firstly display P9. 
a)  Check the U,V, W connection, if is correctness or loose please connect again. 
 
 
 
 
 
 
 
b)  If this code is displayed when the compressor is started for several seconds or even not started, 
check  the compressor connection for correctness, if no insert wrong, replace outdoor PCB. 
11.3.8   Display EU. 
Reason: Voltage sensor damage. 
Solution: Please replace outdoor PCB. 
 
 
 
 
 
 
  
11.3.9   Display EE 
Reason: EEPROM fault. 
Solution: Shut down power supply and reenergize it, if the fault remains there, check the EEPROM 
installation, if no problem, please replace outdoor PCB. 
 
     
 
 
 
11.3.10  Display CL 
  Cause: Air filter duty, the unit operation Cumulative time 500 hours, the controller will confirmation the filter 
dirty and display CL. 
 Solution: Clean the air filter then cut off the power and supply again. 
 
Heat  radiation  problem  easily  happened 
while the screw is not fixed tightly.