TCL Air Conditioner Service Manual
12
2). When switch on unit on cooling mode, ODU fan motor will delay 5s after compressor starts up.
4.1.2.4. When ODU failure or stops for protection, IDU works as preset.
4.1.2.5. Anti-frosting protection
While condition a), b) matched, the AC unit transferred to anti-frosting protection.
a). After the compressor continual works for 6 minutes, and tested IPT≤0 for 3 minutes continuously.
b). After the compressor continual works 6 minutes, and tested IPT≤-2 for 3 seconds continuously.
c). AC unit quit protection while IPT≥10.
4.1.3 Dry mode
4.1.3.1. Temperature control: 16~31.
Fan speed: low
Vane blade position: as customer preset
4.1.3.2. When ODU failure or stops for protection, IDU works as preset.
4.1.3.3. Compressor and process control
1). When RT-ST≥1, the compressor starts up working, AC operates as customer preset;
2). When
a.
RT-ST2, the compressor will start up operation once it stops 3 minutes, and unit without any o
ther
prote
ction or failure code.
b. R
T-ST-2, the compressor will stop working while it works 6 minutes or more continuously
.
c.
-2≤RT-ST≤ 2the compressor will stop working while it works for 6 minutes, after 4 minutes it will
start
workin
g agai
n.
3).
The compressor will also stop working while unit:
a. switched off.
b. under p
rotection.
c. cha
nge
d to fan mode.
4). Und
er normal operation, the compressor can be stopped by program until it works for 6 min at least once starts
up.
5). In the process of unit operation, once the compressor ceased, it should be 3 min delay for the next procedure.
4.1.3.4. ECO and sleep mode: Invalid.
4.1.3.5. Anti-frosting protection
While any of condition a), b), or c) matched, the AC unit transferred to anti-frosting protection.
a). After the compressor continual works for 6 minutes, and tested IPT
≤0 for 3 minutes continuously.
b). After the compressor continual works 6 minutes, and tested IPT
≤-2 for 3 seconds continuously.
c). If the unit works as 6 minutes ON, 4 minutes OFF, and tested IPT≤0 for 3 minutes continuously.
d). AC unit quit protection while IPT≥10.
4.1.4 Heating mode
4.1.4.1. Temperature control: 16-31.
4.1.4.2. Compressor and process control.
1). When ST-CRT≥1, the compressor starts up working, AC operates as customer preset;
2). When
a.
ST-CRT≥1, the compressor will start up operation once it stops 3 minutes, and unit without any other
protection or failure code.
b. ST
-CRT≤-1the compressor will stop working while it works 6 minutes or more continuously
.
c. -1ST
-CRT1the compressor keeps original state.
3). The compressor will also stop working while unit:
a. switched off.
b. under p
rotection.