Control Modes & Auto Tune
E510 provides two control modes
Select the relevant control mode for the application, using parameter 00-00 Control mode.
Default control mode is V/f.
V/f can be used for most applications specifically multi-motor
or applications where auto tune is not successful
or when a customized v/f pattern may be required.
Several V/f patterns are available selectable by parameter 01-00.
Select the appropriate V/f pattern based on the application load type and the motor base
frequency of 50 or 60 Hz.
For selections of the V/f patterns . Refer to the instruction manual.
For Vector modes SLV is used for obtaining best performance from a motor.
V/f Mode Parameters:-
Parameter
Default
Range
Note
01-00
0/9
0-18
0= General Purpose. 50 Hz. System
9= General Purpose. 60Hz. System
For full list of preset patterns set by 01-00,
refer to the manual.
18= Customized V/f.
Set parameters 01-01 to 01-09.
SLV ( vector) mode set parameters in parameter Group 2 .
1) Set the motor parameters highlighted below in Group 2 from motor name plate data.
2) Ensure that the motor is connected correctly then,
3) Enable auto tune function by setting parameter 02-14= 1 ( auto tune Enable).
Auto tune type is Static. No rotation of the motor.
After Auto tune is completed successfully ( no errors) the motor stator & resistance values will
be stored automatically in parameters 02-15 & 02-16.
Group 2 Parameters. Motor data & auto tune
No.
Description
Range
Factory
Setting
Unit
02-00
Motor No Load Current
----
-
Amps(AC)
02-01
Motor Rated Current (OL1)
----
-
A
02-02
Motor rated Slip
Compensation
----
0.0
%
02-03
Motor rated speed
----
-
Rpm
02-04
Motor rated voltage
200V: 170.0~264.0
400V: 323.0~528.0
220.0/440.0
V
02-05
Motor rated power
----
-
KW
02-06
Motor rated frequency
0~650.0
50.0/60.0
Hz
02-07
Motor number of poles.
2 ~16
4
-
02-14
Auto Tune
0: Disable
0
1: Start Auto tune function.
02-15
Stator resistance gain
----
02-16
Rotor resistance gain
----