TECO E510 - Basic Quick Start Parameter List

TECO E510
9 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Downloaded from https://acdriveshop.co.uk
Page 6 of 9 08/08/14
Basic Quick Start Parameter List
Parameter
Default
Range
Note
00-00
0
0-1
0: V/F control mode
1: Vector mode (SLV)
00-14
10.0
0.1~3600.0
Acceleration time in Secs
00-15
10.0
0.1~3600.0
Deceleration time in Secs
00-04
0
0-2
0: Forward/Stop-Reverse/Stop
1: Run/Stop-Reverse/Forward
2: 3-Wire Control Mode-Run/Stop
00-12
50/60Hz
0.01~650.00
Max frequency limit.
00-13
0.0
0.00~649.00
Min frequency limit
00-02
0
0-3
Start mode:-
0: Keypad
1: Remote
2: Communication
3: PLC
00-05
0
0-7
Main frequency source:-
0: Keypad
1: Potentiometer on keypad
2: External AI1 analogue signal
3: External AI2 analogue signal
4: External up/down frequency control
5: Control by Communication method
6: PID output
7: Pulse input
07-09
0
0-1
Stop method:-
0: Decel to stop
1: Coast to stop
02-01
**A
**A
Motor overload protection according to motor
name plate
13-08
0000
Set to factory setting.
1150: 50HZ system
1160: 60HZ system
1112: Reset PLC
Note:- For Full Parameter List see the Instruction manual