Group 00: Basic Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
(F5/F6
Only)(***)
1: ND (Normal
Duty Mode)
00-34 Language
0: English
0 *7
1: Simplified
Chinese
2: Traditional
Chinese
3: Turkish
00-35
Minimum
Frequency
Detection
0: Alarm
0
1: Keep Running
At Lower
Frequency
00-36
PID Lower
Frequency
Selection
0: Disable
(Lower
Frequency of
PID Sleep Mode)
0
1: Enable (0Hz o
PID Sleep Mode)
* : Refer to the following attachment 1
***:If parameter 00-27 is set to ND mode, group 02
motor 1 parameter will automatically adjust to more
than 1 class of it.
If parameter 00-27 is set to HD mode, group 02
motor 1 parameter will automatically adjust to the
same class of it.
It is suggested that parameter 00-27 be set first
before motor performs auto-tuning because the
parameter will make the motor parameter
automatically be changed.
Group 01: V/F Control Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
01-00
Volts/Hz
Patterns
0~FF F
*3
01-02
Maximum
Output
Frequency of
Motor 1
4.8~599.0
50.0/60
.0
*8
01-03
Maximum
Output
Voltage of
Motor 1
200V:
0.1~255.0
230.0
*8
400V:
0.2~510.0
400.0
01-04
Middle Output
Frequency 2
of Motor 1
0.0~599.0 0.0
01-05
Middle Output
Voltage 2 of
Motor 1
200V:
0.0~255.0
0.0 *8
400V:
0.0~510.0
01-06
Middle Output
Frequency 1
of Motor 1
0.0~599.0 2.5/3.0 *8
01-07
Middle Output
Voltage 1 of
200V:
0.0~255.0
KVA *8
Group 01: V/F Control Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Motor 1 400V:
0.0~510.0
01-08
Minimum
Output
Frequency of
Motor 1
0.0~599.0
V/F: 1.3/1.5
SLV: 0.5/0.6
PMSL
V:
10.0
01-09
Minimum
Output
Voltage of
Motor 1
200V:
0.0~255.0
*
*8
400V:
0.0~510.0
01-10
Torque
Compensatio
n Gain
0.0~2.0
0.5
*1
01-11
Selection of
Torque
Compensatio
n Mode
0: Mode 0
(Normal)
0
1: Mode 1
(High Speed)
01-12
Base
Frequency of
Motor 1
4.8~599.0
50.0/60
.0
*8
01-13
Base Output
Voltage of
Motor 1
200V:
0.0~255.0
230.0
*8
400V:
0.0~510.0
400.0
01-14
Input Voltage
Setting
200V:
55.0~255.0
230.0
*8
400V:
10.0~510.0
400.0
01-15
Torque
Compensatio
n Time
0~10000 200
01-16
Maximum
Output
Frequency of
Motor 2
4.8~599.0
50.0/60
.0
*8
01-17
Maximum
Output
Voltage of
Motor 2
200V:
0.1~255.0
230.0
*8
400V:
0.2~510.0
400.0
01-18
Middle Output
Frequency 2
of Motor 2
0.0~599.0 0.0
01-19
Middle Output
Voltage 2 of
Motor 2
200V:
0.0~255.0
0.0
400V:
0.0~510.0
01-20
Middle Output
Frequency 1
of Motor 2
0.0~599.0 2.5/3.0 *8
01-21
Middle Output
Voltage 1 of
Motor 2
200V:
0.0~255.0
KVA *8
400V:
0.0~510.0
01-22
Minimum
Output
Frequency of
Motor 2
0.0~599.0 1.3/1.5
01-23
Minimum
Output
200V:
0.0~255.0
KVA *8