29
Group 16: LCD Function Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
100%.
16-04
Engineering
Unit
0: without
using
engineering
unit
0
*7
1: FPM
2: CFM
3: PSI
4: GPH
5: GPM
6: IN
7: FT
8: /s
9: /m
10: /h
11: °F
12: inW
13: HP
14: m/s
15: MPM
16: CMM
17: W
18: kW
19: m
20: °C
21: RPM
22: Bar
23: Pa
24: kPa
16-05 LCD Backlight 0~7 5 *1*7
16-07
Copy
Function
Selection
0: Do not copy
parameters
0 *7
1: Read
inverter
parameters
and save them
to the operator.
2: Write the
operator
parameters to
inverter.
3: Compare
parameters of
inverter and
operator.
16-08
Selection of
Allowing
Reading
0: Do not allow
to read inverter
parameters or
save them to
the operator.
0 *7
1: Allow to read
inverter
parameters
and save to the
operator.
16-09
Selection of
Operator
Removed
(LCD)
0: Keep
operating when
LCD operator
is removed.
0 *1*7
Group 16: LCD Function Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
1: Display fault
when LCD
operator is
removed
Group 17: Automatic Tuning Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
17-00
Mode
Selection of
Automatic
Tuning*
0: Rotation
Auto-tuning
V/F : 2
SLV : 6
1: Static
Auto-tuning
2: Stator
Resistance
Measurement
3: Reserved
4: Loop Tuning
5: Rotation
Auto-tuning
Combination
(item: 4+2+0)
6: Static
Auto-tuning
Combination
(item: 4+2+1)
17-01
Motor Rated
Output Power
0.00~600.00 KVA
17-02
Motor Rated
Current
0.1~1200.0 KVA
17-03
Motor Rated
Voltage
200V: 50.0~240.0
220
400V: 100.0~480.0
440
17-04
Motor Rated
Frequency
4.8~599.0 60.0
17-05
Motor Rotated
Speed
0~24000 KVA
17-06
Pole Number
of Motor
2~16(Even) 4
17-08
Motor no-load
Voltage
200V: 50~240
KVA
400V:100~480
17-09
Motor
Excitation
Current
0.01~600.00 KVA
17-10
Automatic
Tuning Start
0: Disable
0
1: Enable
17-11
Error History
of Automatic
Tuning
0: No error
0 *4
1: Motor data
error
2: Stator
resistance
tuning error
3: Leakage
induction
tuning error
4: Rotor
resistance
tuning error
5: Mutual

Other manuals for TECO E510s Series