EasyManua.ls Logo

TECO E510s Series - Page 33

TECO E510s Series
78 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
Group 21: Torque And Position Control
Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
22-27
Voltage
Command of
Mode 2
5~120
(22-25=2 or
22-26=1 is
enabled)
50
22-28
Divider Ratio
of Mode 2
0~8
(22-25=2 or
22-26=1 is
enabled)
2
22-29
Flux-weakeni
ng Voltage
Command
Restriction
80~110 (related
to parameter
22-18)
100
22-34
IPM Estimator
Gain
1~300.0
180
Group 23 PUMP & HVAC
Code
Parameter
Name
Setting Range Default
Attribu
te
23-00
Function
Selection
0: Disable
1: PUMP
2: HVAC
3: Compressor
0
23-01
Setting of
Single &
Multiple
Pumps and
Master &
Slave
Machines
0: Single Pump
1: Master
2: Slave 1
3: Slave 2
4: Slave 3
0
23-02
Operation
Pressure
Setting
0.10 ~ 650.00
2.00
23-03
Maximun
Pressure
Setting of
Pressure
Transmitter
0.10 ~ 650.00
10.00
23-04
Pump
Pressure
Command
Source
0Set by 23-02
1Set by AI
0
23-05
Display Mode
Selection
0: Display of
Target and
Pressure
Feedback
1: Target
Pressre Only
2: Feedback
Pressure Only
0
23-06
Proportion
Gain(P)
0.00~10.00 3.00
23-07
IIntegral
Time(I)
0.0~100.0 0.5
Group 23 PUMP & HVAC
Code
Parameter
Name
Setting Range Default
Attribu
te
23-08
Differential
Time(D)
0.00~10.00 0.00
23-09
Tolerance
Range of
Constant
Pressure
0.01 ~ 650.00
0.5
23-10
Sleep
Frequency of
Constant
Pressure
0.00 ~ 599.00
30.00
23-11
Sleep Time of
Constant
Pressure
0.0 ~ 255.5 0.0
23-12
Maximun
Presure Limit
0.00 ~ 650.00 5
23-13
Warning Time
of High
Pressure
0.0 ~ 600.0 10.0
23-14
Stop Time of
High Pressure
0.0 ~ 600.0 20.0
23-15
Minimum
Pressure
Limit
23-20=0 : 0.00
~ 650.00
23-20=1 :
0~100
5
23-16
Warning Time
of Low
Pressure
0.0 ~ 600.0 0.0
23-17
Fault Stop
Time of Low
Pressure
0.0 ~ 600.0 0.0
23-18
Time of Loss
Pressure
Detection
0.0 ~ 600.0 0.0
23-19
Proportion of
Loss
Pressure
Detection
0 ~ 100 0
23-22
Slave Trip
Frequency
0.00 ~ 599.00 45.00
23-23
Direction of
Water
Pressure
Detection
0: Upward
Detection
1: Downward
Detection
1
23-24
Range of
Water
Pressure
Detection
0.00 ~ 65.00 0.1
23-25
PPeriod of
Water
Pressure
Detection
0.0 ~ 200.0 30.0
23-26
Acceleration
Time of Water
Pressure
Detection
0.1 ~ 6000.0 KVA
23-27
Deceleration
Time of Water
Pressure
Detection
0.1 ~ 6000.0 KVA

Other manuals for TECO E510s Series