37
LED display
Possible solutions
EF2 ( flash )
External fault
(S2)
EF3 ( flash )
External fault
(S3)
EF4 ( flash )
External fault
(S4)
EF5 ( flash )
External fault
(S5)
EF6 ( flash )
External fault
(S6)
PI setting error
Check pulse input selection
(03-30) and PID source
(10-00 and 10-01).
FB (flash)
PID feedback
breaking
Check feedback wiring
Replace feedback sensor.
FirE
Fire mode
enabled
Check the environment and
confirm the fire status. If no
fire, turn off the power and
power on again.
PArEr
Parameter
setting error
Please refer to the manual
for correct setting
STP1
Direct start
warning
Remove the run command
from the terminal first, and
enabled later.
LED display
Possible solutions
External
Terminal
Stop Error
Remove the run command
from external terminal
EPErr
EEPROM Save
error
Restore factory setting,
then cut off the power and
power on again.
If warning again, replace
control board.
bdErr
Control board
error
Replace the control board.
Wrong running
direction
Error
Revise the command among
11-00, jog and DI control to
see if any difference
Parameter
Lock
Lifting the parameter lock key
code, to enter the correct
parameter for 13-07
Set password
failed
Enter the correct parameter
for 13-07 to enable the
parameter lock key
Run
Command
Error
Remove the reverse
operation command from
external terminal
ES (flash)
External
Emergency
Stop
Turn off run command, and
remove external emergency
stop command.
Zero Speed
Stop Error
Adjust frequency command