35
Group 03: External Digital Input and
Output Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
2: Allow speed
changes from
last set
frequency when
stopped
3: Refresh
frequency at
acceleration.
03-28
Photo-coupler
Output (DO1-
DOG)
Range and
definition are the
same as those of
03-11, 03-12
(03-28 Set to 8
is pulse output
function)
0
03-29
Photo-coupler
Output
Selection
(DO1-DOG)
(DO2-DOG)
xx0xb: Photo-
coupler 2 A
Contact
xx1xb: Photo-
coupler 2 B
Contact
0000b
*10
03-30
Selection of
Pulse Input
0: General Pulse
Input
0
1: PWM
03-31
Scale of
Pulse Input
Depending on
the setting of 03-
30
03-30 = 0:
50~32000Hz
03-30 = 1:
10~1000Hz
1000 *1
03-32
Pulse Input
Gain
0.0~1000.0 100 *1
03-33
Pulse Input
Bias
-100.0~100.0 0.0 *1
03-34
Filter Time of
Pulse Input
0.00~2.00 0.1 *1
03-35
Function
Setting of
Pulse Output
1: Frequency
Command
2 *1
2: Output
Frequency
3: Output
Frequency
after Soft-Start
4: Motor Speed
5: PID Feedback
6: PID Input
7: PG Output
(with PG card)
03-36
Scale of
Pulse Output
1~32000 1000 *1
03-37
Timer ON
Delay (DIO)
0.0~6000.0 0.0
03-38
Timer OFF
Delay (DIO)
0.0~6000.0 0.0
Group 03: External Digital Input and
Output Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
03-39 Reserved
03-40
Up/Down
Frequency
Width Setting
0.00~5.00 0.00
03-41
Torque
Detection
Level
0~150 10
03-42
Brake
Release
Delay Time
0.00~65.00 0.00
03-43
UP/DOWN
Acceleration/
Deceleration
Selection
0: Acceleration/
Deceleration
Time 1
0
1: Acceleration/
Deceleration
Time 2
03-44
Frequency
Detection
Level 2
0.0~599.0 0.0
03-45
Frequency
Detection
Width 2
0.1~25.5 2.0
03-46
Frequency
Detection
Level 3
0.0~599.0 0.0
03-47
Frequency
Detection
Width 3
0.1~25.5 2.0
03-48
Low Current
Detection
Level
0.0~999.9 0.1 Note2
03-49
Low Current
Detection
Delay Time
0.00~655.34
(Note4)
0.01 Note2
03-50
Frequency
Detection
Level 4
0.0~599.0 0.0 Note3
03-51
Frequency
Detection
Level 5
0.0~599.0 0.0 Note3
03-52
Frequency
Detection
Level 6
0.0~599.0 0.0 Note3
03-53
Current
Agree Level 2
0.0~999.9 0 Note4
03-54
counter ON
delay
0~12 0
03-55
counter OFF
delay
0~12 0
* 2-wire operation mode: 29; 3-wire operation mode:
26.
* *If the maximum output frequency of motor is over
300HZ, the frequency resolution is changed to 0.1Hz
Note: For standard H & C type frame 1, the DO2