EasyManua.ls Logo

TECO E710-403-H3SF - Page 43

TECO E710-403-H3SF
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42
Group 07: Start /Stop Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
2: Execute a
Speed Search
each time
07-33
Start
Frequency of
Speed
Search
Selection
0: Maximum
Output
Frequency of
Motor
0
1: Frequency
Command
07-34
Start short-
circuit braking
time
0.00~100.00 0.00 Note1
07-35
Stop Short-
circuit braking
time
0.00~100.00 0.50 Note1
07-36
Short-circuit
braking
current limited
0.0~200.0 100.0 Note1
07-37
~
07-41
Reserved
07-42
Voltage Limit
Gain
0.0~50.0 0 Note2
07-43
Short-circuit
Braking Time
of PM Speed
Search
0.00~100.00 0.00 Note3
07-44
DC Braking
Time of PM
Speed
Search
0.00~100.00 0.00 Note3
07-45
STP2
Function
Selection
0: STP2 Enable
0 Note4
1: STP2 Disable
07-46
DC Injection
Current Limit
0~150 100 Note5
07-47
PM Speed
Switching
Frequency
Mode
0: Disabled
0 Note8
1: Mode 1
2: Mode 2
*07-13 Low Voltage Detection Level, it is enable when
07-30 Low Voltage Level Selection set 0 (Enable) and
lower frequency limit set to 250V.This application is
for Emergency power supply (EPS)
* *If the maximum output frequency of motor is over
300HZ, the frequency resolution is changed to 0.1Hz
Group 08: Protection Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
08-00
Stall
Prevention
Function
xxx0b: Stall
prevention is
enabled in
acceleration.
0000b
xxx1b: Stall
prevention is
Group 08: Protection Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
disabled in
acceleration.
xx0xb: Stall
prevention is
enabled in
deceleration.
xx1xb: Stall
prevention is
disabled in
deceleration.
x0xxb: Stall
prevention is
enabled in
operation
x1xxb: Stall
prevention is
disabled in
operation
0xxxb: Stall
prevention in
operation is based
on deceleration
time of speed-
stage 1.
1xxxb: Stall
prevention in
operation is based
on deceleration
time of speed-
stage 2.
08-01
Stall
Prevention
Level in
Acceleration
20~200 150
08-02
Stall
Prevention
Level in
Deceleration
200V: 330V~410V
385V
400V: 660V~820V
770V
575V:900~1000
950V
690V:1080~1200
1140V
08-03
Stall
Prevention
Level in
Operation
30~200 160
08-04 Reserved
08-05
Selection for
Motor
Overload
Protection
(OL1)
xxx0b: Overload
Protection is
disabled.
0001b
xxx1b: Overload
Protection is
enabled.
xx0xb: Cold Start
of Motor
Overload
xx1xb: Hot Start
of Motor
Overload
x0xxb: Standard
Motor
x1xxb: Inverter
Duty Motor
0xxxb: Reserved
1xxxb: Reserved

Related product manuals