Group 08: Protection Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
08-06
Start-up
Mode of
Overload
Protection
Operation
(OL1)
0: Stop Output
after Overload
Protection
0
1: Continuous
Operation after
Overload
Protection.
08-07
Motor
Overload
(OL1)
Protection
Level
0: Motor
Overload (OL1)
Protection 0
0 Note2
1: Motor
Overload (OL1)
Protection 1
2: Motor
Overload (OL1)
Protection 2
08-08
Automatic
Voltage
Regulation
(AVR)
0: Enable
0
1: Disable
08-09
Selection of
Input Phase
Loss
Protection
0: Disable
0
1: Enable
08-10
Selection of
Output Phase
Loss
Protection
0: Disable
0
1: Enable
08-11
08-12
Reserved
08-13
Selection of
Over-Torque
Detection
0: Over-Torque
Detection is
Disabled.
0
1: Start to Detect
when Reaching
the Set
Frequency.
2: Start to Detect
when the
Operation is
Begun.
08-14
Selection of
Over-Torque
Operation
0: Deceleration
to Stop when
Over Torque is
Detected.
0
1: Display
Warning when
Over Torque is
Detected. Go on
Operation.
2: Coast to Stop
when Over
Torque is
Detected
08-15
Level of Over-
Torque
Detection
0~300 150
08-16
Time of Over-
Torque
Detection
0.0~10.0 0.1
Group 08: Protection Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
08-17
Selection of
Low-Torque
Detection
0: Low-Torque
Detection is
Disabled.
0
1: Start to Detect
when Reaching
the Set
Frequency.
2: Start to Detect
when the
Operation is
Begun.
08-18
Selection of
Low-Torque
Operation
0: Deceleration
to Stop when
Low Torque is
Detected.
0
1: Display
Warning when
Low Torque is
Detected. Go on
Operation.
2: Coast to Stop
when Low
Torque is
Detected
08-19
Level of Low-
Torque
Detection
0~300 30
08-20
Time of Low-
Torque
Detection
0.0~10.0 0.1
08-21
Limit of Stall
Prevention in
Acc over
Base Speed
1~100 50
08-22
Stall
Prevention
Detection
Time in
Operation
2~100 100
08-23
Ground Fault
(GF)
Selection
0: Disable
0
1: Enable
08-24
External Fault
Operation
Selection
0: Deceleration
to Stop
0
1: Coast to Stop
2: Continuous
Operation
08-25
Detection
Selection of
External Fault
0: Immediately
Detect when the
Power is
Supplied.
0
1: Start to Detect
when the
Operation is
Started.
08-26
~
08-29
Reserved