46
Group 10: PID Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
10-08
AI1
Frequency
Limit
0.00~599.00 0 Note2
10-09 PID Bias -100.0~100.0 0 *1
10-10
PID Output
Delay Time
0.00~10.00 0.00 *1
10-11
PID Feedback
Loss
Detection
Selection
0: Disable
0 1: Warning
2: Fault
10-12
PID Feedback
Loss Det. Lev.
0~100 0
10-13
PID Feedback
Loss Det.
Time
0.0~10.0 1.0
10-14
PID Integral
Limit
0.0~100.0 100.0 *1
10-15
PID Trim
Mode
0~2 0 Note2
10-16
PID Trim
Scale
0~100 100 Note2
10-17
*Start
Frequency of
PID Sleep
0.00~599.00 0.00
10-18
Delay Time of
PID Sleep
0.0~255.5 0.0
10-19
*Frequency of
PID Waking
up
0.00~599.00 0.00
10-20
Delay Time of
PID Waking
up
0.0~255.5 0.0
10-21
10-22
Reserved
10-23
PID Output
Limit
0.00~100.0 100.0 *1
10-24
PID Output
Gain
0.0~25.0 1.0
10-25
PID Reversal
Output
Selection
0: No Allowing
Reversal Output
0
1: Allow
Reversal Output
10-26
PID Target
Acceleration/
Deceleration
Time
0.0~25.5 0.0
10-27
PID Feedback
Display Bias
0~9999 0
10-28 Reserved
10-29
PID Sleep
Selection
0: Disable
1 1: Enable
2: set by DI
10-30
Upper Limit of
PID Target
0.0 ~ 100.0 100.0
10-31
Lower Limit of
PID Target
0.0 ~ 100.0 0.0
10-32 Reserved
Group 10: PID Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
10-33
Maximum
Value of PID
Feedback
1 ~ 10000 999
10-34
PID Decimal
Width
0 ~ 4 1
10-35 PID Unit
0: %
0 *7
1: FPM
2: CFM
3: SPI
4: GPH
5: GPM
6: IN
7: FT
8: /s
9: /m
10: /h
11: °F
12: inW
13: HP
14: m/s
15: MPM
16: CMM
17: W
18: KW
19: m
20: °C
21: RPM
22: Bar
23: Pa
24: KPa
10-36
Proportional
Gain 2 (P)
0.00~10.00 3.00 Note2
10-37
Integral Time
2 (I)
0.00~100.00 0.50 Note2
10-38
Differential
Time 2 (D)
0.00~10.00 0.00 Note2
10-39
*Output
Frequency
Setting of PID
Disconnection
00.00~599.00 30.00
10-40
Selection of
PID forced
Sleep
Frequency
0: Disable
0
1: Enable
10-41
PID Mode
Switch
0: General PID
0 Note2
1: D Type PID
10-42
~
10-46
Reserved
10-47
Proportional
Gain 3(P)
0.00~10.00 3.00 Note4
10-48
Integral Time
3(I)
0.00~100.00 0.50 Note4
10-49
Differential
Time 3(D)
0.00~10.00 0.00 Note4
* If the maximum output frequency of motor is over
300HZ, the frequency resolution is changed to 0.1Hz