47
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
11-00
Direction Lock
Selection
0: Allow
Forward and
Reverse
Rotation
0
1: Only Allow
Forward
Rotation
2: Only Allow
Reverse
Rotation
11-01
Carrier
frequency
2~16: 2~16KHz * *1
11-02
Soft PWM
Function
Selection
0: Disable
1: Soft PWM 1
2: Soft PWM 2
0
11-03
Automatic
carrier lowering
selection
0: Disable
1: Enable
0
11-04
S-curve Time
Setting at the
Start of
Acceleration
0.00~2.50 0.20
11-05
S-curve Time
Setting at the
Stop of
Acceleration
0.00~2.50 0.20
11-06
S-curve Time
Setting at the
Start of
Deceleration
0.00~2.50 0.20
11-07
S-curve Time
Setting at the
Stop of
Deceleration
0.00~2.50 0.20
11-08
Jump
Frequency 1
0.0~599.0 0.0
11-09
Jump
Frequency 2
0.0~599.0 0.0
11-10
Jump
Frequency 3
0.0~599.0 0.0
11-11
Jump
Frequency
Width
0.0~25.5 1.0
11-12
Manual Energy
Saving Gain
0~100 80
11-13
Automatic
Return Time
0~120 60 *1
11-14
~
11-17
Reserved
11-18
Manual Energy
Saving
Frequency
0.0~599.0 0.00
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
11-19
Automatic
Energy Saving
Function
0: Automatic
energy saving
is disabled.
0
1: Automatic
energy saving
is enabled.
11-20
Filter Time of
Automatic
Energy Saving
0~200 140
11-21
Voltage Upper
Limit of Energy
Saving Tuning
0~100 100
11-22
Adjustment
Time of
Automatic
Energy Saving
0~5000 20 *1
11-23
Detection Level
of Automatic
Energy Saving
0~100 10
11-24
Coefficient of
Automatic
Energy Saving
0.00~655.34
(Note4)
-
11-25 Reserved
11-26
Carrier Output
Frequency
Tuning Upper
Limit (%)
10~100 80
11-27
Carrier Output
Frequency
Tuning Lower
Limit (%)
2~100 20
11-28
Frequency
Gain of Over
Voltage
Prevention 2
1~200 100
11-29
Auto De-rating
Selection
0: Disable
1: Enable
0
11-30
Variable Carrie
r
Frequency
Upper Limit
2~16 -
11-31
Variable Carrie
r
Frequency
Lower Limit
1~16 -
11-32
Variable Carrie
r
Frequency
Proportional
Gain
00~99 00
11-33
DC Voltage
Filter Rise
Amount
0.1~10.0 0.1 *1
11-34
DC Voltage
Filter Fall
Amount
0.1~10.0 5.0 *1
11-35
DC Voltage
Filter Dead
band Level
0.0~99.0 10.0 *1
11-36
Frequency
Gain of OV
Prevention
0.000~1.000 0.050 *1