48
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
11-37
**Frequency
Limit of OV
Prevention
0.00~599.00 5.00
11-38
Deceleration
Start Voltage of
OV Prevention
200V: 200~400V
300
400V: 400~800V
700
575V: 500~1000V
900
690V: 600~1200V
1080
11-39
Deceleration
Stop Voltage of
OV Prevention
200V: 300~400V
350
400V: 600~800V
750
575V: 500~1000V
950
690V: 600~1200V
1140
11-40
OV Prevention
Selection
0: Disable
0
1: OV Prevention
Mode 1
2: OV Prevention
Mode 2
3: OV Prevention
Mode 3
4: OV Prevention
Mode 4
11-41
Selection of
Reference
Frequency
Disappearance
Detection
0: Decelerate
to Stop when
Reference
Frequency
Disappears
0
1: Operation is
set by
Parameter 11-
42 when
Reference
Frequency
Disappears
11-42
Disappearance
Level of
Reference
Frequency
0.0~100.0 80.0
11-43
Hold
Frequency at
Start
0.0~599.0 0.0
11-44
Frequency
Hold Time at
Start
0.0~10.0 0.0
11-45
Hold
Frequency at
Stop
0.0~599.0 0.0
11-46
Frequency
Hold Time at
Stop
0.0~10.0 0.0
11-47
KEB
Deceleration
Time
0.0~25.5 0.0 *1
11-48
KEB Detection
Level
200V: 190~210 200
400V: 380~420 400
575V: 540~570 555
690V: 540~684 555
11-49
Zero-servo
Gain
0.01~5.00 1.00
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
11-50
Zero-servo
Count
0~4096 12
11-51
Braking
Selection of
Zero Speed
0: Disable
0
1: Enable
11-52
Droop Control
Level
0.0~100.0% 0.0 *1
11-53
Droop Control
Delay
0.01~2.00 0.2 *1
11-54
Initialization of
Cumulative
Energy
0: Do not Clear
Cumulative
Energy
0 *1
1: Clear
Cumulative
Energy
11-55
STOP Key
Selection
0: Stop Key is
Disabled when
the Operation
Command is
not Provided
by Operator.
1
1: Stop Key is
Enabled when
the Operation
Command is
not Provided
by Operator.
11-56
UP/DOWN
Selection
0: When
UP/DOWN in
Keypad is
Disabled, it will
be Enabled if
Pressing
ENTER after
Frequency
Modification.
0
1: When
UP/DOWN in
Keypad is
Enabled, it will
be Enabled
upon
Frequency
Modification.
11-57 Reserved
11-58
Record
Reference
Frequency
0: Disable
0 *1
1: Enable
11-59
Gain of
Preventing
Oscillation
0.00~2.50 *
11-60
Upper Limit of
Preventing
Oscillation
1~100 *
11-61
Time
Parameter of
Preventing
Oscillation
0~100 0