49
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
11-62
Selection of
Preventing
Oscillation
0: Mode1
-
1: Mode2
2: Mode3
11-63
Strong
Magnetic
Selection
0: Disable
1
1: Enable
11-64
Acceleration
Speed Gain
Adjustment
0.1~10.0 1.0
11-65
Target Main
Circuit Voltage
200V: 200V~400V
370
400V: 400V~800V
740
575V: 520V~1040V
962
690V: 624V~1248V
1154
11-66
2 Phase/ 3
Phase PWM
Switch
Frequency
6.00~60.00 20 Note2
11-67
Soft PWM 2
Frequency
Range
0~12000 0 Note2
11-68
Soft PWM 2
Switch
Frequency
6.00~60.00 20 Note2
11-69
Gain of
Preventing
Oscillation 3
0.00~200.00 - Note1
11-70
Upper Limit of
Preventing
Oscillation 3
0.01~100.00 5.00 Note1
11-71
Time
Parameter of
Preventing
Oscillation 3
0~30000 100 Note1
11-72
Gain of
Preventing
Oscillation for
switch
frequency 1
0.01~300.00 - Note1
11-73
Gain of
Preventing
Oscillation for
switch
frequency 2
0.01~300.00 - Note1
11-76
Droop
Frequency
Level 1
0.00~599.00 0.00 Note4
11-77
Droop
Frequency
Level 2
0.00~599.00 0.00 Note4
11-78
Droop Torque
Offset Value
0.00~100.00 0.00 Note4
11-79
LOC/REM
Keypad Button
Selection
0: Forward /
Reverse
control
1: Local /
Remote
control
0
11-80
Local / Remote
selection mode
0: Mode 1
Allow direct
0
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
switching
1: Mode 2
No switching
in operation
2: Mode 3
Stop running
after switching
11-81
OVP4 Level
(%)
1.00~2.00 1.10
11-82 OVP4 Gain 0~256 64
*: Refer to the attachment 1 in our instruction manual..
** If the maximum output frequency of motor is over
300HZ, the frequency resolution is changed to 0.1Hz
Note: The parameter of 11-01 can be changed during run
operation, the range is 1~16KHz.
Group 12: Monitoring Parameters
Code
Parameter
Name
Setting Range Default
Attrib
ute
12-00
Display Screen
Selection (LED)
00000~77777
From the
leftmost bit, it
displays the
screen when
press DSP key
in order.
0:no display
1: Output Current
2: Output Voltage
3: DC Bus
Voltage
4: Heatsink
Temperature*
5: PID Feedback
6: AI1 Value
7: AI2 Value
00321
(Note4)
1
*6
12-01
PID Feedback
Display Mode
(LED)
0: Display the
Feedback
Value by
Integer (xxx)
0 *6
1: Display the
Feedback
Value by the
Value with One
Decimal Place
(xx.x)
2: Display the
Feedback
Value by the
Value with Two
Decimal
Places (x.xx)
12-02
PID Feedback
Display Unit
Setting (LED)
0: xxxxx (no
unit)
0 *6
1: xxxPb
(pressure)
2: xxxFL (flow)