EasyManua.ls Logo

TECO E710-403-H3SF - Page 68

TECO E710-403-H3SF
146 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
67
When the inverter detects a warning, the
keypad displays a warning code (flash).
Note: The fault contact output does not
energize on a warning and the inverter
continues operation. When the warning is no
longer active the keypad will return to its
original state.
When the inverter detected a programming
error (for example two parameters contradict
each other of are set to an invalid setting), the
keypad displays a self-diagnostics code.
Note: The fault contact output does not
energize on a self-diagnostics error. While a
self-diagnostics code is active the inverter
does not accept a run command until the
programming error is corrected.
Note: When a warning or self- diagnostic error
is active the warning or error code will flash on
the keypad. When the RESET key is pressed,
the warning message (flash) disappears and
returns after 5 sec. If the warning or self-
diagnostic error still exists.
Refer to Table 4.2 for and overview, cause and
corrective action for inverter warnings and self-
diagnostic errors.
Table 4.2 warning / self-diagnosis and corrective
actions
LED display Corrective action
OV
(flash)
Over voltage
Increase deceleration
time
Reduce input voltage to
comply with the input
voltage requirements or
install an AC line
reactor to lower the
input voltage.
Remove the power
factor correction
capacitor.
Use dynamic braking
unit.
Replace braking
transistor or resistor.
Adjust speed search
parameters.
UV
(flash)
under voltage
Check the input voltage.
Check input wiring.
Increase acceleration
LED display Corrective action
time.
Check power source
Replace pre-charge
contactor
Replace control board
or complete inverter.
OH1
Heatsink
overheat
Install fan or AC to cool
surroundings.
Replace cooling fan.
Reduce carrier
frequency.
Reduce load / Measure
output current
OH2
(flash)
Inverter over
heating
warning
Multi-function input
function set incorrectly.
Check wiring
OT
(flash)
over torque
detection
Check over torque
detection parameters
(08-15 / 08-16).
Check and reduce
motor load, check and
operation duty cycle.
UT
(flash)
under torque
detection
Check under torque
detection parameters
(08-19 / 08-20).
Check load /
application.
bb1
(flash)
External
baseblock
Multi-function input
function set incorrectly.
Check wiring
bb2
(flash)
External
baseblock
bb3
(flash)
External
baseblock
bb4

Related product manuals