23
Group 13 Inspection & Maintenance
functions
No. Description Range
Factory
Setting
Note
13-00
Drive
Horsepower
Code
--- - *3
13-01
Software
ersion
--- - *3*4
13-02
Fault Log
(Last 3
Faults)
--- - *3*4
13-03
ccumulated
Operation
ime1 1
0~23 - *3
13-04
ccumulated
Operation
ime1 2
0~65535 ---- *3
13-05
ccumulated
Operation Time
Mode
0: Time Under
Power
1: Run Mode Time
Only
0 *3
13-06
Parameter
Lock
0: Enable all
Functions
1: Preset speeds
05-01~05-08
cannot be changed
: All Functions
cannot be changed
Except for Preset
peeds
05-01~05-08
3: Disable All
Function
0
13-07
Parameter
Lock Code
00000~65535 00000
13-08
Reset Drive
o Factory
Settings
1150: Initialization
(50Hz,220V/380V)
1250/1
360
(Note)
1160: Initialization
(60Hz,220V/380V)
1250: Initialization
(50Hz,230V/400V)
1260: Initialization
(60Hz,230V/460V)
1350: Initialization
(50Hz,220V/415V)
1360: Initialization
(60Hz,230V/400V)
Notes:
For built-in EMC filter models, the default setting of
13-08 is “1250”.
For without built-in EMC filter models, the default
setting of 13-08 is “1360”
Group 14 PUMP Application Function
No. Description Range
Factory
Setting
Note
14-00
Function
Selection
0: Disable
1: PUMP
0 Note1
14-01
Setting of
Single &
Multiple
Pumps and
Master &
Slave
Machines
0: Single Pump
1: Master
: Slave 1
3: Slave 2
: Slave 3
0 Note1
14-02
Operation
Pressure
Setting
0.1~(the value of
14-03)
.00 Note1
14-03
Maximum
Pressure
Setting of
Pressure
ransmitter
0.10 ~ 650.00 10.00 Note1
14-04
Pump
Pressure
Command
Source
0:Set by 14-02
1:Set by AI
0 Note1
14-05
Display
Mode
Selection
0: Display of
arget and
Pressure
Feedback
(14-03<99)
1: Target Pressure
Only
: Feedback
Pressure Only
0 Note1
14-06
Proportion
Gain(P)
0.00~10.00 3.00 Note1
14-07
IIntegral
ime(I)
0.0~100.0 0.5 Note1
14-08
Differential
ime(D)
0.00~10.00 0.00 Note1
14-09
olerance
Range of
Constant
Pressure
hen 14-20=0,
range is
0.00~650.00
hen 14-20=1,
range is 0~100
5 Note1
14-10
Sleep
Frequency
f Constant
Pressure
0.00~599.00 30.00 Note1
14-11
Sleep Time
f Constant
Pressure
0.0~255.5 0.0 Note1
14-12
Maximun
Presure
Limit
hen 14-20=0,
range is
0.00~650.00
hen 14-20=1,
range is 0~100
50 Note1
14-13
arning
ime of High
Pressure
0.0~600.0 10 Note1
14-14
Stop Time o
High
Pressure
0.0~600.0 20 Note1
14-15
Minimum
hen 14-20=0, 5 Note1