EasyManua.ls Logo

TECO L510S Series - Chapter 2 Part Number Definition; 2.1 Model Part Number

TECO L510S Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6
2.2.3 Three phase (NPN) input
MCCB
L1
L
AC
source
S2
S3
S4
AO
3
+
250VAC/1A
(30VDC/1A)
T1
T2
T3
RB
RA
S5
L3 N
ON-OFF
Surge
Suppressor
10V
AVI
ACI
GND
MC
Magnetic
Contactor
RS485
FWD (Run/Stop)
REV (Run/Stop)
Speed Control
External speed
potentiometer = 10 Kohm
or PID input
Induction
Motor
COM
MC
Thermal
relay
MC
S1
GND
0~10V
2
AO
+
-
Frequency
Indicator
0~10VDC
CON2
Thermal
relay
M
0~20mA
P
P'
2'
1
-
Relay
Output
Pin 1 to Pin 8
Ground
Inverter
output
Power
input
Analog
Output
Multifunction
Input
Terminals
Analog
Input
L2
Note:
Earth wire of CON2
must be connected
Model:
200V : L510-2P2-SH3-N(P), L510-2P5-SH3-N(P), L510-201-SH3-N(P)
L510-202-SH3-N(P), L510-203-SH3-N(P), L510-205-SH3(P)
400V : L510-401-SH3-N(P), L510-402-SH3-N(P), L510-403-SH3-N(P)
1:Data+
2:Data-
3:Data+
4:Reserved
5:Reserved
6:Data-
7:5V
8:GND

Other manuals for TECO L510S Series