20
Group 08- Drive & Motor Protection
functions
No. Description Range
Factory
Setting
Note
08-07
Over heat
Protection
(cooling fan
control)
0: Auto (Depends
o
n temp.)
1: Operate while in
RUN mode
2
: Always Run
3: Disabled
1
08-08
A
VR
Function
(Auto
V
oltage
Regulation)
0: AVR function
enable
1: AVR function
Disable
2
: AVR function
d
isable for stop
3: AVR function
d
isable for
d
eceleration
4
: AVR function
d
isable for stop
and deceleration.
5: When
V
DC>(360V/740V)
, AVR function
d
isable for stop
and deceleration.
4
08-09
Input phase
lost
protection
0: Disabled
1: Enabled
0
08-10
PTC
Overheat
Function
0: Disable
1: Decelerate to
s
top
2
: Coast to stop
3: Continue
running, when
w
arning level is
reached.
Coast to stop,
w
hen protection
level is reached.
0
08-11
PTC Signal
Smoothing
T
ime
0.01~10.00 0.2
08-12
PTC
Detection
T
ime Delay
1~300 60
08-13
PTC
Protection
Level
0.1~10.0 0.7
08-14
PTC
Detection
Level Rese
t
0.1~10.0 0.3
08-15
PTC
W
arning
Level
0.1~10.0 0.5
08-16
Fan Control
T
emperatur
e Level
10.0~50.0 50.0
08-17
Over current
protection
level
0.0 ~ 60.0 0.0
Group 08- Drive & Motor Protection
functions
No. Description Range
Factory
Setting
Note
08-18
Over current
protection
t
ime
0.0 ~ 1500.0 1.0
08-19
Motor
Overload
Protection
Level
0: Motor Overload
Protection Level 0
1: Motor Overload
Protection Level 1
2
: Motor Overload
Protection Level 2
0
Group 09- Communication function
setup
No. Description Range
Factory
Setting
Note
09-00
A
ssigned
Communica
t
ion Station
Number
1 ~ 32 1 *2*3
09-01
Communica
t
ion Mode
Selec
t
0: Modbus RTU
code
1: Modbus ASCII
code
2
: BACnet
0 *2*3
09-02
Baud Rate
Setting
(bps)
0 :4800
1: 9600
2
: 19200
3: 38400
4
: Remote Control
is enabled
2
*2*3
09-03
Stop Bit
Selection
0: 1 Stop Bit
1: 2 Stop Bits
0 *2*3
09-04
Parity
Selection
0: Without Parity
1: With Even Parit
y
2
: With Odd Parity
0 *2*3
09-05
Data Forma
t
Selection
0: 8-Bits Data
1: 7-Bits Data
0 *2*3
09-06
Communica
t
ion time-out
d
etection
t
ime
0.0 ~ 25.5 0.0
09-07
Communica
t
ion time-out
o
peration
s
election
0: Deceleration to
s
top (00-15:
Deceleration time 1)
1: Coast to stop
2
: Deceleration to
s
top (00-17:
Deceleration time 2)
3: continue
o
perating
0
09-08
Error 6
v
erification
t
ime.
0 ~ 20 3
09-09
Drive
T
ransmit
d
elay Time
ms
5 ~ 65 5
09-10
BACnet
s
tations
1~254 1 *2*3