23
Group12 Digital Display & Monitor
functions
No. Description Range
Factory
Setting
Note
Display Unit
Setting
2
: xxxfl (flow)
12-03
Custom
Units (Line
Speed)
V
alue
0~65535
1500/180
0
*1
12-04
Custom
Units (Line
Speed)
Display
Mode
0: Drive Output
Frequency is
Displayed
1: Line Speed.
Integer.(xxxxx)
2
: Line
Speed..One
Decimal Place
(xxxx.x)
3: Line Speed.Two
Decimal Places
(xxx.xx)
4
: Line
Speed.Three
Decimal Places
(xx.xxx)
0 *1
12-05
Inputs and
o
utpu
t
Logic status
d
isplay
( S1 to S5)
&
RY1
----- *4
12-06
Output
Power ----
0.0
12-07
Motor
Current
Percentage
---- 0
Group 13 Inspection & Maintenance
functions
No. Description Range
Factory
Setting
Note
13-00
Drive
Horsepower
Code
-
--- - *3
13-01
Software
V
ersion
-
--- - *3*4
13-02
Fault Log
(Last 3
Faults)
-
--- - *3*4
13-03
A
ccumulated
Operation
T
ime1 1
0~23 - *3
13-04
A
ccumulated
Operation
T
ime1 2
0~65535 ---- *3
13-05
A
ccumulated
Operation Time
Mode
0: Time Under
Power
1: Run Mode Time
Only
0 *3
Group 13 Inspection & Maintenance
functions
No. Description Range
Factory
Setting
Note
13-06
Parameter
Lock
0: Enable all
Functions
1: Preset speeds
05-01~05-08
cannot be changed
2
: All Functions
cannot be changed
Except for Preset
speeds
05-01~05-08
3: Disable All
Function
4
: Parameters
00-00 cannot be
modified, cannot
be restored to
f
actory settings,
other parameters
can be changed
0
13-07
Parameter
Lock Code
00000~65535 00000
13-08
Reset Drive
t
o Factory
Settings
1150: Initialization
(50Hz,220V/380V)
1160: Initialization
(60Hz,220V/380V)
1250: Initialization
(50Hz,230V/400V)
1260: Initialization
(60Hz,230V/460V)
1350: Initialization
(50Hz,220V/415V)
1360: Initialization
(60Hz,230V/400V)
1250/1
360
(Note)
Notes:
For built-in EMC filter models, the default setting of
13-08 is “1250”.
For without built-in EMC filter models, the default
setting of 13-08 is “1360”
Group 14 PUMP Application Function
No. Description Range
Factory
Setting
Note
14-00
Function
Selection
0: Disable
1: PUMP
0
14-01
Setting of
Single &
Multiple
Pumps and
Master &
Slave
Machines
0: Single Pump
1: Multiple pumps
-
Master
2
: Multiple pumps
-
Slave 1
3: Multiple pumps
-
Slave 2
4
: Multiple pumps
-
Slave 3
0
14-02
Operation
Pressure
Setting
0.1~(the value of
14-03)
4.00
14-03
Maximum
Pressure
0.10 ~ 650.00 10.00

Other manuals for TECO L510S Series