24
Group 14 PUMP Application Function
No. Description Range
Factory
Setting
Note
Setting of
Pressure
T
ransmitter
14-04
Pump
Pressure
Command
Source
0Set by 14-02
1Set by AI
0
14-05
Display
Mode
Selection
0: Display of
T
arget and
Pressure
Feedback
(14-03<99)
1: Target Pressure
Only
2
: Feedback
Pressure Only
0
14-06
Proportion
Gain(P)
0.00~10.00 3.00
14-07
Integral
T
ime(I)
0.0~100.0 0.5
14-08
Differential
T
ime(D)
0.00~10.00 0.00
14-09
T
olerance
Range of
Constant
Pressure
W
hen 14-20=0,
range is
0.00~650.00
W
hen 14-20=1,
range is 0~100
5
14-10
Sleep
Frequency
o
f Constant
Pressure
0.00~599.00 30.00
14-11
Sleep Time
o
f Constant
Pressure
0.0~255.5 0.0
14-12
Maximum
Pressure
Limit
W
hen 14-20=0,
range is
0.00~650.00
W
hen 14-20=1,
range is 0~100
50
14-13
W
arning
T
ime of High
Pressure
0.0~600.0 10
14-14
Stop Time o
f
High
Pressure
0.0~600.0 20
14-15
Minimum
Pressure
Limit
W
hen 14-20=0,
range is
0.00~650.00
W
hen 14-20=1,
range is 0~100
5
14-16
W
arning
T
ime of Low
Pressure
0.0~600.0 0.0
14-17
Fault Stop
T
ime of Low
Pressure
0.0~600.0 0.0
14-18
T
ime of Los
s
Pressure
Detection
0.0~600.0 0.0
14-19
Proportion 0~100 0
Group 14 PUMP Application Function
No. Description Range
Factory
Setting
Note
o
f Loss
Pressure
Detection
14-20
Switching of
Pressure
and
Percentage
0: Pressure
1: Percentage
1
14-22
Slave Trip
Frequenc
y
0.00 ~ 599.00 45.00
14-23
Direction of
W
ater
Pressure
Detection
0: Upward
Detection
1: Downward
Detection
1
14-24
Range of
W
ater
Pressure
Detection
W
hen 14-20=0,
range is
0.00~650.00
W
hen 14-20=1,
range is 0~100
1
14-25
Period of
W
ater
Pressure
Detection
0.0~200.0 30.0
14-26
A
cceleration
T
ime of
W
ater
Pressure
Detection
0.1~3600.0 12.0
14-27
Deceleration
T
ime of
W
ater
Pressure
Detection
0.1~3600.0 35.0
14-28
Forced Run
Command
0.00~(the value of
00-12)
0.00
14-29
Switching
T
ime of
W
ater
Pressure
Detection
0~240 3
14-30
Detection
T
ime of
Multiple
Pumps in
Parallel
Running
Start
0~30.0 0.0
14-31
Synchronou
s
Selection
o
f Multiple
Pumps in
Parallel
0: Disable
1: Pressure Setting
Run/Stop
2
: Pressure Setting
3: Run/Stop
1
14-34
T
olerance
Range of
Constant
Pressure 2
W
hen 14-20=0,
range is
0
.00~650.00
W
hen 14-20=1,
range is 0~100
5
14-35
Selection of
Multiple
Pumps Shift
Operation
0: No Function
1: Timer
A
lternately
Selection
1