Group 14 PUMP Application Function
No. Description Range
Factory
Setting
Note
2
: Sleep Stop
A
lternately
Selection
3: Timer and Sleep
S
top Alternately
Selection
4
: Multiple Pumps
T
est Mode
14-37
Leakage
Detection
T
ime
0.0~100.0 0.0
14-38
Pressure
V
ariation of
Leakage
Detection
Restar
t
W
hen 14-20=0,
range is
0.00~65.00
W
hen 14-20=1,
range is 0~100
1
14-39
Pressure
T
olerance
Range of
Leakage
Detection
Restar
t
W
hen 14-20=0,
range is
0.00~650.00
W
hen 14-20=1,
range is 0~100
5
14-71
Maximum
Pressure
Setting
0.10~650.00 10
14-72
Switching
T
ime of
A
lternation
in Parallel
0: Hour
1: Minute
0
14-73
Slave
W
ake-Up
Selection
0: Disable
1: Enable
0
14-74
Proportion
T
ime 2 (P)
0.00~10.00 3.00
14-75
Integral
T
ime 2 (I)
0.0~100.0 0.5
14-76
Differential
T
ime 2 (D)
0.00~10.00 0.00
14-77
T
he Value o
f
W
ater
Pressure
Detection
0~100 1
14-78
Maximum
Current
Limit
0
.1~6553.5 6.1
14-79
Minimum
Current
Limit
0
.1~6553.5 6.1
14-80
Current
limit
cumulative
time
0
~600.0 0
**(Group 14 only can be used once parameter
14-00=1)
Note: When 14-00 set to 1, 07-12 will be set to 0 at
the same time. (After version 1.13)
Chapter 4
Troubleshooting and
maintenance
4.1 Error display and corrective
action
4.1.1 Manual Reset and Auto-Reset
Faults which cannot be recovered
manually
Display Corrective action
-OV-
Consult with the supplier
-LV-
1.Check if the power
voltage is correct
2. failed resistor or fuse
3. Consult with the supplier
-OH-
Improve the ventilation
conditions, if no result then
replace the inverter
OH-C
1. Reduce carrier
frequency
2. Improve the ventilation
conditions, if no result
then replace the inverter
CtEr
Consult with the supplier
HPErr
Check the inverter
capacity setting (13-00) to
meet the hardware voltage
levels.
Err4
1.Remove the interference
source then restart by
switching power OFF/ON
2 If not resolved then
Consult with the supplier
EPr
Consult with the supplier
COt
Check the wiring