EasyManua.ls Logo

TECO T-verter N2 Series - Peripheral Application Precautions; Power Supply and Protection Devices; Power Improvement and Noise Filtering; Inverter Terminal Connections

TECO T-verter N2 Series
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
Precautions for peripheral applications:
Power source:
z Make sure the voltage applied is correct to avoid damaging
the inverter.
z A molded-case circuit breaker must be installed between
the AC source and the inverter.
Molded-case circuit breaker:
z Use a molded-case circuit breaker that conforms to the
rated voltage and current of the inverter to control the
power ON/OFF and protect the inverter.
z Do not use the inverter as the switch for run/stop switching.
Leakage breaker:
z Install a leakage breaker to prevent error operation caused
by electric leakage and to protect operators.
Magnetic contactor:
z Normal operations do not need a magnetic contactor. But a
contactor has to be installed when performing functions
such as external control and auto restart after power
failure, or when using brake controller.
z Do not use the magnetic contactor as the run/stop switch
of the inverter.
Reactor for power improvement:
z When inverters below 200V/400V 15KW are supplied with
high capacity (above 600KVA) power source, a reactor
can be connected to improve the power performance.
Input noise filter:
z A filter must be installed when there are inductive load
around the inverter.
Inverter:
z Input power terminals L1, L2, and L3 can be used in any
sequence regardless of phases.
z Output terminals T1, T2, and T3 are connected to U, V,
and W terminals of the motor. If the motor is reversed while
the inverter is forward, just swap any two terminals of T1,
T2, and T3.
z To avoid damaging the inverter, do not connect the input
terminals T1, T2, and T3 to AC power.
Connect the ground terminal properly. 200V class: Ground
to 100Ω or less, 400V class: Ground to 10Ω or less.
Power
Molded-case
Magnetic
contactor
AC reactor
for power
Input noise
filter
Ground
Three-phase
cage motor
N
2 inverte
r
Ground