38
Fn_24: Jog Speed Reference = 0 - 400 Hz
Fn_25: Master Speed Reference from Keypad = 0 - 400 Hz.
Note:
1. The T-verter will be operating under the Jog Speed function at (Fn_24) you can assign either
(Fn_56) (Fn_57) or (Fn_58) to handle the jog function.
2. The T-verter will operate under the Pre-set speed frequencies when (Fn_56) (Fn_57) or
(Fn_58) are assigned to this function.
3. If the process timer in (Fn_84) is turned on and (Fn_56) (Fn_57) or (Fn_58) have been
assigned for input functions, if a pulse signal or contact closure is received on the
multi-function input, the T-verter will run at the pre-set time based on the setting in (Fn_85)
(Fn_86) (Fn_87) (Fn_88) (Fn_89) (Fn_90) and (Fn_91), The sequence will continue until all
process timers are finished, the T-verter will then returns to the frequency set by keypad or
an external Speed Pot or jump back to 0 speed to receive the next sequence.
4. A New speed setting or timer sequence cannot be inserted during an active sequence.
Pre-set Speed
Terminal 6
Pre-set Speed
Terminal 7
Pre-set Speed
Terminal 8
Jog Terminal Output
frequency (Hz)
Operation time
X X X X Fn_25
O X X X Fn_17 Fn_85
X O X X Fn_18 Fn_86
O O X X Fn_19 Fn_87
X X O X Fn_20 Fn_88
O X O X Fn_21 Fn_89
X O O X Fn_22 Fn_90
O O O X Fn_23 Fn_91
-- -- -- O Fn_24
O: TERMINAL ON X: TERMINAL OFF --: NO EFFECT