EasyManua.ls Logo

TECO T-verter N2 Series - Jog and Master Speed References (Fn_24, Fn_25); Note on Speed References

TECO T-verter N2 Series
83 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38
Fn_24: Jog Speed Reference = 0 - 400 Hz
Fn_25: Master Speed Reference from Keypad = 0 - 400 Hz.
Note:
1. The T-verter will be operating under the Jog Speed function at (Fn_24) you can assign either
(Fn_56) (Fn_57) or (Fn_58) to handle the jog function.
2. The T-verter will operate under the Pre-set speed frequencies when (Fn_56) (Fn_57) or
(Fn_58) are assigned to this function.
3. If the process timer in (Fn_84) is turned on and (Fn_56) (Fn_57) or (Fn_58) have been
assigned for input functions, if a pulse signal or contact closure is received on the
multi-function input, the T-verter will run at the pre-set time based on the setting in (Fn_85)
(Fn_86) (Fn_87) (Fn_88) (Fn_89) (Fn_90) and (Fn_91), The sequence will continue until all
process timers are finished, the T-verter will then returns to the frequency set by keypad or
an external Speed Pot or jump back to 0 speed to receive the next sequence.
4. A New speed setting or timer sequence cannot be inserted during an active sequence.
Pre-set Speed
Terminal 6
Pre-set Speed
Terminal 7
Pre-set Speed
Terminal 8
Jog Terminal Output
frequency (Hz)
Operation time
X X X X Fn_25
O X X X Fn_17 Fn_85
X O X X Fn_18 Fn_86
O O X X Fn_19 Fn_87
X X O X Fn_20 Fn_88
O X O X Fn_21 Fn_89
X O O X Fn_22 Fn_90
O O O X Fn_23 Fn_91
-- -- -- O Fn_24
O: TERMINAL ON X: TERMINAL OFF --: NO EFFECT