45
Fn_51: Display Mode Selection 1 ~ 5
The Display contents can be switched back and forth using the key either in the run
mode or stop mode.
Frequency/ RPM / Line speed (Mode set by (Fn_51)
Fxxx (Parameters setting mode: refer to digital operator illustration)
Output voltage DC voltage (Output voltage, DC voltage
(Output current), power set-up at
(Fn_47)
Output current
Fn_52: Line Speed Display 1 ~ 0-9999
120 freq.
(RPM) = x frequency ; Line speed = xFn_52 (decimal digits
Fn_36 Fn_06 decided by Fn_51)
Fn_53: DC Braking Time 0.1 ~ 0 to 25.5 Sec.
Fn_54: DC Braking Injection Frequency 0.1 ~ 0.1 to 10 Hz
Fn_55: DC Braking level 0.1 % ~ 0 to 20 %
Fn_56 ~ Fn_58: Multifunction Inputs
Note:
The application parameters in the Multifunction Input list are all assignable on TM2.
Terminals (6) (7) and (8) are the designated application terminals for the following features.