47
09 Control signal selection
Multi-input terminal OFF: Operation command/ Freq command is from digital operator or remote
control (TM2), according to the setting of Fn_10 / Fn_11
Multi-input terminal ON: Operation command/ Freq command is from digital operator regardless
of the setting of Fn_10 / Fn_11
10 Communication control mode selection
Multi-input terminal OFF: During communication, Inverter can receive Rnu/Freq signals from
control unit (PC or PLC), Parameter can be changed by control unit, Run/Freq signals from
Keypad and TM2 will be ineffective, Keypad can be used for displaying Voltage / Current /
Frequency or emergency stop but can not be used for changed parameters
Multi-input terminal ON: During communication, The Rnu/Freq command is controlled by
Inverter itself, Control unit (PC or PLC) is just for reading parameters.
11 Accel/Decel Prohibit
The T-verter will stop accelerating or decelerating when Accel. / Decel. Prohibit signal is
activated. When the signal is removed, the T-verter continues accelerating or decelerating.
Run
Command
Accel./Decel. (*)
Prohibit
Output
*: When the “Run” command is off, the Accel and Decel prohibit command is inactive.