Fn_65: Skip Frequency 1 0.01 Hz ~ 0 to 400 Hz
Fn_66: Skip Frequency 2 0.01 Hz ~ 0 to 400 Hz
Fn_67: Skip Frequency 3 0.01 Hz ~ 0 to 400 Hz
Fn_68: Frequency Band Width 0.01 Hz ~ 0 to 10 Hz
Example:
When (Fn_65) is set at 10.0 Hz, (Fn_66) is set at 20.0 Hz, (Fn_67) is at 30.0 Hz, (Fn_68)
Skip bandwidth at 2.0 Hz
The skip freq. ranges are: 10 Hz
±
2 Hz = 8 - 12 Hz
20 Hz
±
2 Hz = 18 -22 Hz
30 Hz
±
2 Hz = 28 - 32 Hz
Fn_69: Electronic Overload Protection
xxx0: Electronic thermal motor protection activated
xxx1: Electronic thermal motor protection deactivated
xx0x: Electronic thermal characteristics in accordance with standard motor
xx1x: Electronic thermal characteristics in accordance with special motor
x0xx: Motor protection OL: 103% continues, 150% for one minute
x1xx: Motor protection OL: 113% continues, 123% for one minute
0xxx: Free run to stop after electronic thermal motor protection is energized
1xxx: Operation continued after electronic thermal motor protection is energized
Fn_70: (Motor Rated Current) (- - - - -)
Note:
1. You must enter the motors Rated nameplate current in function (Fn_70) for proper thermal
protection.