z DIGITAL OPERATOR REMOTE CABLE (NW300X) for N2-2P5~205, N2-401~405
2.Installation:
(1) Turn off the power, make sure the T-verter power indicator (LED101) is off.
(2) Remove digital operator 2 and grounding wires (PE) from T-verter.
(3) Put the digital operator 2 into plastic housing 1 , 3 , then use screw 8 to
assemble the housing as shown above.
(4) Put the remote cable adapter 5 into the T-verter.
(5) Connect terminal 4 of remote cable to adapter 5 , and connect the grounding wire
as well.
(6) Connect the other side terminal 7 of remote cable to adapter 5 ,and connect the
grounding wire as well.
(7) Use accessory screws 6 ,to fix the remote operator to the panel.
(8) To avoid interference, proper grounding on T-verter enclosure is necessary.
(grounding resistance must be less than 100Ω,diameter of grounding wire must
be bigger than 2mm
2
)
1. Contents:
(1) Plastic housing for digital
operator:
1 front side
3 rear side
(2) Remote cable: 4
NW3001 (1m)
NW3002 (2m)
NW3003 (3m)
(3) Remote cable adapter 5
(4) Accessory screws 6 , 8
(5) Digital operator 2
NDOP-01