1)
It is possible to go back to the previous step by pressing the MODE button.
2)
If, when pressing ENT, "Err" is displayed, it means that one of the following errors have been made:
ALARM ≥ TRIP or FAN-OFF ≥ FAN-ON. Press PRG to go back to step 1 and correct the data.
3)
After 1 minute's keyboard inactivity programming is abandoned without saving the data.
4)
At the end of programming the FAULT relay is disabled till the control unit is restarted.
5)
During programming the control unit does not control/protect the monitored machine.
ATTENTION:
We recommend you check the control unit before starting the device.
The default parameters set by TECSYSTEM might not suit your requirements.
Programming the device is the end user’s responsibility: the set alarm thresholds and the enabled functions
described in this manual must be checked (by a specialized technician) referring them to the application and
system characteristics on which the control unit is installed.