T154 SERIES
T154 /UL/ T154 FAHRENHEIT
STEP
PRESS
EFFECT
PRESS
NOTES
1
Keep the PRG button pressed till the PRG-ON LED
lights up. After PRG the ALARM threshold for CH 1-2-3
is displayed
2
Set the desired threshold
Default 90°C (194°F)
3
The TRIP threshold for CH 1-2-3 is displayed
4
Set the desired threshold
Default 119°C (246 °F)
5
The CH 4 LED flashes
CH 4 enabling
6
Set YES or NO
with YES CH 4 is ON, with
NO CH 4 is OFF
7
The ALARM threshold for CH 4 is displayed
If CH 4=NO go to step
11, Default NO
8
Set the desired threshold
Default 120°C (248 °F)
9
The TRIP threshold for CH 4 is displayed
10
Set the desired threshold
Default 140°C (284 °F)
11
The Fan LED flashes and the channel LEDs ventilation
refers to light up
Default Ch1-Ch2-Ch3
12
Select NO, CH 1-2-3 or CH 4 (if CH 4
YES)
NO: fan disabled,
go to step 22
13
ON is displayed
FAN switching on
14
The ON threshold of the FANS is displayed
15
Set the desired threshold
Default 70°C(158°F)
16
OFF is displayed
FAN switching off
17
The OFF threshold of the FANS is displayed
18
Set the desired threshold
Default 60°C(140 °F)
PROGRAMMING

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the TECSYSTEM T154 Series and is the answer not in the manual?

TECSYSTEM T154 Series Specifications

General IconGeneral
BrandTECSYSTEM
ModelT154 Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals