T154 SERIES
TECHNICAL
SPECIFICATIONS
T154
T154 UL
T154
FAHRENHEIT
T154 –4
T154 –4
FAHRENHEIT
TEST AND PERFORMANCE
Protection from electrical interference EN 61000-4-4
●
●
●
●
●
Dielectric strength 1500 Vac for one min. between output
relays and sensors, relays and power supply, power supply
and sensors
●
●
●
●
●
Accuracy ±1% full scale value, ±1 digit
●
●
●
●
●
Ambient operating temperature from –20°C to +60°C
●
●
●
●
●
Humidity 90% non-condensing
●
●
●
●
●
Housing NORYL 94 _V0
●
●
●
●
●
Absorption 4VA
●
●
●
●
●
Data storage: 10 years minimum
●
●
●
●
●
Digital linearity of sensor signal
●
●
●
●
●
Self-diagnostic circuit
●
NO
NO
NO
NO
Electronic protection only on customer's
request.
Option
Option
Option
Option
Option
Vibration test IEC 68-2-6 Width ±1 mm from 2Hz to 13.2Hz
Acceleration ±0.7G from 13.2 Hz to 100 Hz
●
●
●
●
●
(*) Seismic test according to IEEE 344-1.987
●
●
●
●
●
DISPLAY AND DATA MANAGEMENT
1 x 13 mm display with 3 digits to display temperatures and
messages.
●
●
●
●
●
4 LEDs to show the selected channel
●
●
●
●
●
4 LEDs to show the alarm status of the selected channel
●
●
●
●
●
Temperature control from 0°C to + 200°C
●
NO
NO
NO
NO
Temperature control from 0°C to + 240°C (32°F-464°F)
Option
●
●
●
●
2 alarm thresholds for channels 1-2-3
●
●
●
NO
NO
2 alarm thresholds for channel 4
●
●
●
NO
NO
2 ON-OFF thresholds for FAN control
●
●
●
●
●
Individually programmable alarm thresholds for each channel
NO
NO
NO
●
●
Sensor diagnostics (Fcc-Foc-FCd)
●
●
●
●
●
Data storage diagnostics (Ech)
●
●
●
●
●
Access to programming through front keyboard
●
●
●
●
●
Automatic exit from programming after 1 minute's inactivity
●
●
●
●
●
Incorrect programming warning
●
●
●
●
●
Selection of automatic channel scanning, hottest channel or
manual scanning
●
●
●
●
●
Storage of maximum temperatures reached by channels and
alarm status
●
●
●
●
●
Front alarm reset button
●
●
●
●
●