- 16 -
setting with "Set" there will be a security prompt and after
confirming with "+" an acknowledgement will be displayed (OK).
Displays the software version
Information only for the manufacturer
8. Status of slab heating
Operating state of the slab heating (On/Off)
Operating hour counter for heating 1, can be reset
Operating hour counter for heating 2, cannot be reset
Reset counter 1 and start counter again from 0
9. Sensor test
Displays operating state of selected sensor
Displays current temperature of selected sensor
Displays remaining time before the next moisture detection cycle can begin
Starts moisture detection for the selected sensor. Adapt setting with "Set" and then "+" / "-
". After selecting "Yes" and setting with "Set" an acknowledgement will be displayed (OK).
Only possible if measuring method "F" or "T+M" are set and no moisture measurement is
ongoing for another sensor. The inhibit time until the next measurement is interrupted
when this command is given. .
Displays the last measured moisture value of the selected sensor
10. Sensor configuration
Displays the setting of the connected sensor type for the selected
sensor; adapt setting with "Set" and then "+" / "-"; save with "Set".
When saving the sensor type, the appropriate measurement method
of the selected sensor is set automatically to the method specified for
the sensor and the sensor state is reset automatically.
3351,
3352/53,
3354,
3355,
3356
31xx,
---
Displays the setting of the measurement method for the selected
sensor; adapt setting with "Set" and then "+" / "-"; save with "Set".
"OFF" = sensor not in service,
" T " = only temperature,
" M " = only moisture,
"T+M" = temperature and moisture
The measurement methods "M" and "T+M" are not available for
temperature-only sensors (depending on the set sensor type). When
saving the measurement method, the sensor state is reset
automatically.