Item Field Range Description
0 to 255, 0 to 255, 0
to 255, 0 to 255
Default:
127,127,127,127
Access: Adv
BACNET BBMD IP
Sets the BBMD IP address on the BACnet
®
network. The address is set using four
number sets displayed in the source output fields. Touch the ‘Next Item’ button to
view and adjust each number set.
Note: This item is only available when BAS TYPE is set to BACn and BBMD TIME
is not set to OFF.
0x1 to 0xFFFF
Default: 0xBAC0
(47808)
Access: Adv
BACNET BBMD PORT
Sets the BBMD UDP port on the BACnet
®
network.
Note: This item is only available when BAS TYPE is set to BACn and BBMD TIME
is not set to OFF.
BACnet
®
Settings in the 284 BAS Menu