Repeater Installation and Programming Manual
6
9
15
6.6. Silencing the Internal Buzzer
The internal buzzer of the Repeater is signaling in case of activated alarm or fault events in the system. The
buzzer silencing is available from every access level without code entry.
To silence the internal buzzer press button.
6.7. Silencing the Sounders
The sounders silencing is available from access levels 2 and 3 after code entry.
To silence the sounders enter in sequence:
Maintenance Code 2222
Installer Code 3333
The LED ‘Silence sounders’ right to the button is lighting up.
To reset the panel in normal operation mode press ‘Reset’ button.
6.8. Activate Evacuation
The evacuation alert is available for activation from every access level regarding the following:
Level 1: Just for that cases, when the fire alarm signal is received from a detector in a zone.
To start the sounders for evacuation alert, the user has to press the button.
Levels 2 and 3: In case there is no fire alarm signal from a detector in a zone.
To start the sounders for evacuation alert, the user has to enter in sequence:
Maintenance Code 2222
Installer Code 3333
6.9. Resetting the Panel
The resetting of the panel’s current state is available from access levels 2 and 3 after code entry. The
resetting function is used for initializing the panel and return to normal operation mode after alarm or fault
restoring.
To reset the panel enter in sequence:
Maintenance Code 2222
Installer Code 3333
After resetting are cleared also all introduced earlier test in zones and disablements. The introduced delays
are not cleared. The panel returns to normal operation mode.
6.10. Indication Test
The indication test could be started at any time regardless of the access level. The general test allows the
user to review the correct operation of the LED indication on the front panel, the sound signal of the internal
buzzer, and the visualization on the LCD display.
To start the general test press button all LEDs must light on and the internal buzzer starts sounding.
On the LCD module every one position is displayed with 5x8 dots. The panel will automatically exit the
general test mode after 6 seconds. The general test can be stopped also with next pressing of the same
button.