TEMP-HEAT
®
Shut-Down Steps
Short-Term Shut Down
Turn burner switch to OFF position.
Wait 30-sec.
Turn blower switch to OFF position.
Look to see that flame is extinguished.
Extended Shut-down or Disconnection of Unit
With unit running, close vapor-fuel supply valve at vaporizer. (Propane installation only.)
Caution: Do not close liquid supply valve while vaporizer is ON. See vaporizer for proper
operation of vaporizer. Contact your gas company for further information on safe handling
of propane vaporizers.
Allow heater to run until flame-safety light goes ON, indicating that all gas has been burned
from gas lines.
Caution: Check to see that pilot light on vaporizer is extinguished before disconnecting gas lines.
Turn burner switch OFF.
Continue running blower until no flame exists in the base of the burner.
Turn the blower switch OFF.
Turn power OFF at source and disconnect electrical lines.
Disconnect propane-vapor line from heater.
Contact gas company to disconnect vaporizer.