EasyManua.ls Logo

Temp-Heat THP-400A - THP Series Rating Information

Default Icon
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5
TEMP-HEAT
®
Rating Information
For indoor or outdoor installation
Unit Specifications THP-400A THP-500A THP-550
CFM 2,500 3,000 3,000
BTU/Hour minimum
maximum
200,000
400,000
44,500
500,000
40,500
550,000
Inlet Pressure
Natural Gas
minimum psig
maximum psig
1/2
4*
1/4
4*
1/2
4*
Inlet Pressure
Propane Gas
maximum psig 10 10 10
Electrical Requirements voltage/hertz/phase/amps 115/60/1/20 115/60/1/20 115/60/1/20
Dimensions l x w x h, in 50 x 26 x 48 58 x 28 x 53 56 x 29 x 40
Weight lbs 450 565 500
Minimum distance from
combustible materials
floor, in
top, in
sides, in
discharge, ft
0
6
6
10
0
6
6
10
0
6
6
10
Ambient Conditions minimum
o
F
maximum
o
F
-40
120
-40
120
-40
120
*For inlet pressure over 4-psi natural gas, contact TEMP-AIR.