Fuel Supply System — Bulk-Tank System
Installation must comply with all state and local codes or, in the absence of local codes, with the
standard for the Storage and Handling of Liquified Petroleum Gases, ANSI/NFPA 58.
Locate fuel tanks according to the minimum distances shown in the Rating Information
Table on page 5.
The vapor-supply fuel line from the tank or vaporizer must have a first-stage regulator located
at the tank or vaporizer to reduce the tank pressure to the 10-psi needed to supply unit.
A vaporizer may be necessary, especially on multiple-heater installations where adequate storage
supply is not attainable or practicable.
Vaporizers must be no closer than 10-ft from a container.
Locate vaporizers at a minimum of 15-ft from fuel-transfer valves.
Typical Vaporizer Installation — Algas 40/40 Vaporizer
Each Storage Capacity
above Ground
Minimum Distance
from Building
one, 500-gal tank 10-ft
one or two, 1000-gal tanks 25-ft
2001-gal or more 50-ft