TEMP-HEAT
®
Fuel Supply System — Bulk-Tank System
• Installation must comply with all state and local codes or, in the absence of local codes, with the
standard for the Storage and Handling of Liquified Petroleum Gases, ANSI/NFPA 58.
• Locate fuel tanks according to the minimum distances shown in the Rating Information
Table on page 5.
• The vapor-supply fuel line from the tank or vaporizer must have a first-stage regulator located
at the tank or vaporizer to reduce the tank pressure to the 10-psi needed to supply unit.
• A vaporizer may be necessary, especially on multiple-heater installations where adequate storage
supply is not attainable or practicable.
• Vaporizers must be no closer than 10-ft from a container.
• Locate vaporizers at a minimum of 15-ft from fuel-transfer valves.
Typical Vaporizer Installation — Algas 40/40 Vaporizer
Each Storage Capacity
above Ground
Minimum Distance
from Building
one, 500-gal tank 10-ft
one or two, 1000-gal tanks 25-ft
2001-gal or more 50-ft