THP-400A, THP-500A and THP-550 Installation and Service Manual
Set-Up
Keep fresh-air intake and heated-air discharge clear of obstruction.
Provide clearance to allow access to vestibule, blower, and motor compartments.
Heater must be level and in compliance with minimum-clearance and minimum-distance
requirements for combustible materials. See Rating Information Table on page 5.
Position heater to draw 100% fresh, outside air through its intake grill.
Do not use or operate the heater in the presence of combustible vapors or liquids.
Maintain a maximum voltage differential of plus or minus 10% while unit is running.
Do not move, handle, or service heater while hot, running, or connected to power supply.
Check for gas leaks and proper functioning during installation, periodically, or when relocating.
Typical Heater Installation
Natural Gas Installations
See Rating Information Table on page 5 for proper inlet pressure.
Use external regulator supplied on all installations over 4-psi.
Gas meter and supply system must be able to supply the minimum supply pressures as specified
in the Rating Information Table on page 5.
Follow all federal, state, and local codes governing temporary-gas connections.
Leak test all gas connections using a 1:3 solution of soap and water.