EasyManua.ls Logo

Tempco tec-920 - Chapter 7 Modbus Communications; Functions Supported

Default Icon
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25
Chapter 7 Modbus Communications
Function 03: Read Holding Registers
Query: (from Master) Response: (from Slave)
Slave address (0-255)
Function code (3)
Starting address of register Hi (0) Byte count
Starting address of register Lo Data 1 Hi
(0-79, 128-131) Data 1 Lo
No. of words Hi (0) Data 2 Hi
No. of words Lo (1-79) Data 2 Lo
CRC16 Hi
CRC16 Lo
CRC16 Hi
CRC16 Lo
Function 06: Preset Single Register
Query: (from Master) Response: (from slave)
Slave address (0-255)
Function code (6)
Register address Hi (0)
Register address Lo (0-79, 128-131)
Data Hi
Data Lo
CRC16 Hi
CRC16 Lo
Function 16: Preset Multiple Registers
Query: ( from master ) Response: (from slave)
Slave address (0-255)
Function code (16)
Starting address of register Hi (0)
Starting address of register Lo (0-79, 128-131)
No. of words Hi (0)
No. of words Lo (1-79)
Byte count (2-158) CRC16 Hi
Data 1 Hi CRC16 Lo
Data 1 Lo
Data 2 Hi
Data 2 Lo
CRC16 Hi
CRC16 Lo
This chapter specifies the Modbus Communications protocol as
RS-232 or RS-485 interface module is installed. Only RTU mode is supported. Data is transmitted
as eight-bit binary bytes with 1 start bit, 1 stop bit and optional parity checking (None, Even or
Odd). Baud rate may be set to 2400, 4800, 9600, 14400, 19200, 28800 and 38400.
7-1 Functions Supported
Only function 03, 06 and 16 are available for this series of controllers. The message formats for
each function are described as follows:

Related product manuals