Recommended Maintenance Service for Temtrol Equipment
Type of Service Start-Up Monthly Every 6 Months Shutdown Annually
Inspect General Condition of Unit XX
Clean Debris From Unit XX X
Check and Adjust Fan Belt Tension XX
Check Unit for Unusual Noise or Vibration XX
Check Fan Bearing Locking Collars XX
Check Motor Voltage and Current XX
Lubricate Fan Shaft Bearings X See Below X
Lubricate Motor Base Adjusting Screws XXX
Check Fan for Rotation Without Obstruction X
Check Fan for Proper Rotation X
Inspect Protective Finish X
Replace Filters X
Lubricate Damper Linkage X
Check Fans for Unusual Vibration XX
Clean Outside of Coils XX
IMPORTANT SAFETY NOTES
Before performing any maintenance or inspection, make certain that all power has been
disconnected.
Adequate precautions should be taken to safeguard the equipment and the premises from
damage, also the public from possible injury as appropriate for the installation of these
products.
SPEED TEMPERATURE CLEANLINESS
100 RPM Up to 120 degrees F Clean
500 RPM Up to 150 degrees F Clean
1000 RPM Up to 180 degrees F Clean
1500 RPM Over 210 degrees F Clean
Any Speed Up to 150 degrees F Dirty
Any Speed Over 150 degrees F Dirty
Any Speed Any Temperature Very Dirty
Any Speed Any Temperature Extreme Cond.
MAINTENANCE
FREQUENCY SCHEDULE
The following table should be used as a relubrication guide:
Conditions
Add grease slowly with shaft rotating, until a slight bead forms at the seals.
GREASE INTERVAL
6 to 12 months
2 to 6 months
2 wks to 2 months
Weekly
Daily to 2 wks
Daily to 2 wks
Daily to 2 wks
Daily to 2 wks