PROBLEM PROBABLE CAUSE
Coil Does Not Deliver Lack of chilled water Chilled water pump undersized or malfunctioning
Adequate Cooling
Dirty finned tubes Vacuum or use air hose to gently clean dirt from
finned tubes
Coil undersized Replace with larger coil
Coil Leaks Crack in brazed connection Repair brazed joint
Internal corrosion Replace coil
Moisture on Walls Excess capicity through Check air flow through coil
Downstream of Cooling cooling coil
Coil
Standing water in drain pan See "Condensate Drain Pan" Section
V.A.V. unit (Low Volume Air Verify that the air flow and water flow are synchronized
Flow - High Volume Water
Flow)