750W SERIES DC POWER SUPPLY
PU SERIES
PU6-100 6V/100A PU8-90 8V/90A
PU12.5-60
12.5V/60A PU20-38 20V/38A
PU30-25
3V/25A PU40-19 40V/19A
PU60-12.5
60V/12.5A PU80-9.5 80V/9.5A
PU100-7.5
100V/7.5A PU150-5 150V/5A
PU300-2.5
300V/2.5A PU600-1.3 600V/1.3A
INSTRUCTION MANUAL
© PRINTED IN JAPAN B65-0166-00

Table of Contents

Questions and Answers

  • K
    Katherine CollinsSep 23, 2025
    What causes poor load regulation on TEXIO Power Supply with CV LED on?
    • J
      Joe McdonaldSep 23, 2025
      If you're experiencing poor load regulation on your TEXIO Power Supply and the front panel CV LED is on, it could be due to improperly connected sensing wires. Ensure that the sense wires are connected according to the user’s manual instructions.
  • N
    nealericaAug 23, 2025
    How to troubleshoot a TEXIO PU Power Supply with no output and blank displays?
    • R
      robertbrownAug 23, 2025
      First, check if the AC power cord is defective by checking its continuity and replacing it if necessary. Also, verify that the AC input voltage is within the acceptable range and connect the power supply to an appropriate voltage source.
  • T
    Thomas GriffinAug 25, 2025
    What to do if my TEXIO PU Power Supply output is present momentarily but shuts off quickly and the display indicates “AC”?
    • M
      Mark HallAug 26, 2025
      Check the input AC voltage. If the AC source voltage sags when a load is applied, connect the power supply to an appropriate voltage source.
  • L
    Lisa HarrisAug 27, 2025
    Why TEXIO PU output voltage will not adjust and front panel CC LED is on?
    • J
      Joseph BrownAug 27, 2025
      The unit may be in constant current mode. Check the current limit setting and the load current.
  • N
    Nicole PenaAug 27, 2025
    What to do if my TEXIO PU Power Supply output is present momentarily but shuts off quickly and the display indicates “OUP”?
    • H
      Henry SullivanAug 27, 2025
      The power supply might be configured to Remote sense. Check if the positive or negative load wire is loose.
  • Y
    yewingSep 18, 2025
    Why does my TEXIO Power Supply have no output and blank displays?
    • J
      jonathankimSep 18, 2025
      If your TEXIO Power Supply shows no output and all displays and indicators are blank, there could be a couple of reasons: * The AC power cord might be defective: Check its continuity and replace if necessary. * The AC input voltage might be out of range: Verify the input AC voltage and connect to an appropriate voltage source.
  • V
    valerie87Sep 15, 2025
    Why won't the output current adjust on my TEXIO Power Supply when the CV LED is on?
    • V
      Victor EdwardsSep 15, 2025
      If the output current on your TEXIO Power Supply won't adjust and the front panel CV LED is on, it indicates that the unit is in constant voltage mode. Check the current limit and voltage setting.
  • K
    Kyle RiveraSep 16, 2025
    What to do if TEXIO Power Supply output voltage won't adjust and CV LED is on?
    • F
      floresrichardSep 16, 2025
      If the output voltage on your TEXIO Power Supply won't adjust and the front panel CV LED is on, check whether the output voltage is adjusted above the OVP setting or below the UVL setting. Set OVP or UVL so they will not limit the output.
  • B
    Barbara IngramSep 6, 2025
    Why does my TEXIO Power Supply shut off quickly and display 'AC'?
    • J
      Jessica DeckerSep 6, 2025
      If your TEXIO Power Supply output is present momentarily but shuts off quickly, and the display indicates “AC”, it could be due to the AC source voltage sagging when a load is applied. Check the input AC voltage and ensure it's connected to an appropriate voltage source.
  • T
    Todd GoodwinSep 4, 2025
    What to do if my TEXIO Power Supply front panel controls are nonfunctional?
    • E
      Elizabeth KennedySep 4, 2025
      The power supply might be in Local-Lockout mode. Turn off the AC power and wait until the display turns off. Then, turn on the AC power and press the front panel REM/LOC button.

TEXIO PU Series Specifications

General IconGeneral
Operating ModeConstant Voltage (CV) / Constant Current (CC)
TypeDC Power Supply
Output Voltage0 to rated voltage
Output Current0 to rated current
Input Voltage100-240V AC, 50/60Hz
ProtectionOver Voltage Protection (OVP), Over Current Protection (OCP), Over Temperature Protection (OTP)
Current Resolution1mA
Ripple & Noise (CV)≤ 10 mVrms
InterfaceUSB, RS232
Operating Temperature0°C to 40°C
Storage Temperature70 °C
Dimensions215mm (W) x 88mm (H) x 350mm (D)