AMP 400-1000L I&O Manual 15
E. Clearances
found in Table 5
F. Clearances (French)
G. Closet and Alcove Installaon
VI(continued)
Minimum
Clearance
Front
(In.)
Rear
(In.)
Right
(In.)
Left
(In.)
Top
(In.)
Serviceability
(Indoor
Installation)
24 24 0* 0* 0
Serviceability
(Outdoor
Installation)
24 36 0* 0* 0**
To
Combustible
Construction
0 0 0 0 0
* Leave 24" clearance on at least one side.
**
H. Side by Side and 0" Clearance Installaon
24 in
WARNING WARNING