AMP 400-1000L I&O Manual 57
XIII(continued)
WARNING WARNING
2
2
2
2
2
2
2
D. Field Conversion of Gas Type
Table 32
the Naonal Fuel Gas Code
Natural Gas and Propane Installaon
Code
Table 31
Figure 25
Natural Gas LP Gas
AMP
Model
CO
2
% O
2
% CO
2
% O
2
%
400
8.8 5.2
9.8 6.0
500
8.8 5.2
9.8 6.0
650
8.8 5.2
9.8 6.0
800
8.8 5.2
9.8 6.0
1000L
8.8 5.2
9.8 6.0
AMP
Model
Part Number
To Natural Gas To LP Gas
400
111545-01 111544-01
500 111545-02 111544-02
650 111545-03 111544-03
800 111545-04 111544-04
1000L 111545-05 111544-05
AMP
Model
Number of turns from closed
Natural Gas/Propane Gas
400
5
500 1
650 1
800 1
1000L 1