AMP 400-1000L I&O Manual 47
XI(continued)
Specic
Gravity
Correction
Factor
Specic
Gravity
Correction
Factor
0.60 1.00 0.90 0.82
0.65 0.96 1.0 0.78
0.70 0.93 1.10 0.74
0.75 0.90 1.20 0.71
0.80 0.87 1.30 0.68
0.85 0.81 1.40 0.66
C. Gas Pressure Switches
WARNING WARNING
AMP
Model
Inlet Size
(In.)
Min. Gas Pres.
(In. W.C.)
Max. Gas Pres.
(In. W.C.)
High Gas
Pressure Switch
1
(In. W.C.)
Low Gas
Pressure Switch
1
(In. W.C.)
Natural Propane Natural Propane
400 3/4
4 8 14 14 1
Natural: 3
LP: 7
500 3/4
650 1
800 1
1000L 1
1
Factory default high and low gas pressure switch setpoint.
Manual Reset