18 AMP 400-1000L I&O Manual
WARNING WARNING
VII(continued)
Make Stainless Steel Brand Polypropylene Brand
DuraVent FasNSeal PolyPro
Heat Fab Saf-T Vent EZ Seal* -
Z-Flex (Nova Flex Group) Z-Vent Z-DENS
Centrotherm - InnoFlue SW Rigid
Note: Included appliance connection is a 3-in-1 adapter that permits Stainless Steel, Polypropylene, or CPVC.
Adapting to Z-DENS requires 4" increaser 2ZDI44 or 6" adapter 2ZDCPVCG6.
Adapting to InnoFlue requires 4" adapter ISAALE0404 or 6" adapter ISAALE0606
AMP Model
Vent
Diameter (in.)
Style
Heat Fab Part #
Saf-T Vent
DuraVent Part #
FasNSeal
400
500
4
Tee 9490TEE FSTT4
90° Elbow 9414TERM -
Straight 9492 -
23° Elbow - FSBS4
650
800
1000L
6
Tee 9690TEE FSTT6
90° Elbow 9614TERM -
Straight 9692 -
23° Elbow - FSBS6
AMP Model
Vent
Diameter (in.)
Style
DuraVent Part #
PolyPro
Centrotherm Part #
InnoFlue
Z-Flex Part #
Z-DENS
400
500
4
Tee 4PPS-TTBL ISTT0420 2ZDTT4
Elbow 4PPS-E90BC - 2ZDE487UV
Straight 4PPS-12BC ISEP04 2ZDES4
Screen 4PPS-BG IASPP04 2ZDES4
650
800
1000L
6
Tee 6PPS-TTBC ISTT0620 2ZDTT6
Elbow 6PPS-E90BC - 2ZDE687
Straight 6PPS-12BC - 2ZDES6
Screen 6PPS-BG IASPP06 2ZDES6
At Maximum Input Rate At Minimum Input Rate
AMP
Model
Flue Gas Flow, ACFM @
35% Excess Air, 180
0
F
Combustion Air, SCFM
@ 35% Excess Air,
60
0
F
Flue Gas Flow, ACFM @
35% Excess Air, 180
0
F
Combustion Air, SCFM
@ 35% Excess Air,
60
0
F
400 113 92 11 9
500 141 115 14 11
650 183 149 18 15
800 226 184 23 18
1000L 282 212 28 23
Note: Flow rates are based on the combustion of natural gas.