APPENDIX “B”
THOMSON POWER SYSTEMS
©
TS 970 SYSTEM VOLTAGE CHANGE
PROCEDURE
4916 - 275th Street, Langley, BC, Canada V4W 0A3 · Telephone (604) 888-0110
Email: info@thomsonps.com · www.thomsonps.com
CAUTION: Brace PT terminal block with your hand when loosening or tightening ANY screws.
6. Remove the screw and red ring terminal connected to the incorrect (existing) PT
voltage terminal. Install the screw and red ring terminal to the new selected PT Tap
Terminal based on required voltage and tighten while supporting the terminal block.
Make sure the ring terminal is not misaligned or the PT cover will not fit back on.
7. Install the extra screw back onto the old PT location and tighten.
CAUTION
Confirm that PT screws are correctly tightened, and do not put strain
on the PT Tap wires.
8. Replace the PT cover. PT covers should 'snap' in place, confirm they are installed
correctly by gently "twisting" the PT cover. DO NOT use excessive force.
9. Repeat the steps 1 to 5 for all Potential Transformers.
NOTE: 2 to 3 PT’s will be installed in the Transfer Switch depending on the Model