APPENDIX
102
NV10B - Manual - 04 - 2022
Self-test Relay
MINOR Fail alarm NO | YES
Self-test relay K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
MMI
Modules data visualization Assigned modules | All modules
Profile selection
Active profile A | B | By INPUT
Profile A
Thermal protection with RTD thermometric probes - 26
PT1 Probe
ThAL1 Alarm
ThAL1 Enable ThAL1 Enable OFF | ON
26 PT1 Alarm threshold ThAL1 ^C 0 ... 200 step = 1
ThAL1 Operating time
Value s 0 ... 100 step = 1
ThAL1 Alarm relays ThAL1-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
ThAL1 Alarm LEDs ThAL1-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Th>1 Trip
Th>1 Enable Th>1 Enable OFF | ON
26 PT1 Trip threshold Th>1 ^C 0 ... 200 step = 1
Th>1 Operating time
Value s 0 ... 100 step = 1
Th>1 Breaker failure Th>1BF OFF | ON
Th>1 Trip relays Th>1-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Th>1 Trip LEDs Th>1-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
PT2 Probe
ThAL2 Alarm
ThAL2 Enable ThAL2 Enable OFF | ON
26 PT2 Alarm threshold ThAL2 ^C 0 ... 200 step = 1
ThAL2 Operating time
Value s 0 ... 100 step = 1
ThAL2 Alarm relays ThAL2-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
ThAL2 Alarm LEDs ThAL2-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Th>2 Trip
Th>2 Enable Th>2 Enable OFF | ON
26 PT2 Trip threshold Th>2 ^C 0 ... 200 step = 1
Th>2 Operating time
Value s 0 ... 100 step = 1
Th>2 Breaker failure Th>2BF OFF | ON
Th>2 Trip relays Th>2-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Th>2 Trip LEDs Th>2-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
PT3 Probe
ThAL3 Alarm
ThAL3 Enable ThAL3 Enable OFF | ON
26 PT3 Alarm threshold ThAL3 ^C 0 ... 200 step = 1
ThAL3 Operating time
Value s 0 ... 100 step = 1
ThAL3 Alarm relays ThAL3-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
ThAL3 Alarm LEDs ThAL3-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Th>3 Trip
Th>3 Enable Th>3 Enable OFF | ON
26 PT3 Trip threshold Th>3 ^C 0 ... 200 step = 1
Th>3 Operating time
Value s 0 ... 100 step = 1
Th>3 Breaker failure Th>3BF OFF | ON