APPENDIX
107
NV10B - Manual - 04 - 2022
UE>>def Operating time
Value s
0.07 ... 9.99 step = 0.01
10.0 ... 100.0 step = 0.1
Trip circuit supervision - 74TCS
74TCS Enable 74TCS Enable OFF | ON
74TCS Logical block 74TCS-BLK1 OFF | ON
74TCS Start relays 74TCS-ST-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
74TCS Trip relays 74TCS-TR-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
74TCS Start LEDs 74TCS-ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
74TCS Trip LEDs 74TCS-TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Breaker failure - BF
BF Enable BF Enable OFF | ON
BF Time delay
Value s 0.06 ... 10.00 step = 0.01
BF Logical block BF-BLK1 OFF | ON
BF Start relays BF-ST-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
BF Trip relays BF-TR-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
BF Start LEDs BF-ST-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
BF Trip LEDs BF-TR-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Profile B
Thermal protection with RTD thermometric probes - 26
PT1 Probe
ThAL1 Alarm
ThAL1 Enable ThAL1 Enable OFF | ON
26 PT1 Alarm threshold ThAL1 ^C 0 ... 200 step = 1
ThAL1 Operating time
Value s 0 ... 100 step = 1
ThAL1 Alarm relays ThAL1-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
ThAL1 Alarm LEDs ThAL1-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Th>1 Trip
Th>1 Enable Th>1 Enable OFF | ON
26 PT1 Trip threshold Th>1 ^C 0 ... 200 step = 1
Th>1 Operating time
Value s 0 ... 100 step = 1
Th>1 Breaker failure Th>1BF OFF | ON
Th>1 Trip relays Th>1-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
Th>1 Trip LEDs Th>1-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
PT2 Probe
ThAL2 Alarm
ThAL2 Enable ThAL2 Enable OFF | ON
26 PT2 Alarm threshold ThAL2 ^C 0 ... 200 step = 1
ThAL2 Operating time
Value s 0 ... 100 step = 1
ThAL2 Alarm relays ThAL2-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10
ThAL2 Alarm LEDs ThAL2-L
START | TRIP | L1 | L2 | L3 | L4 | L5 | L6 | L7 | L8
| L9 | L10
Th>2 Trip
Th>2 Enable Th>2 Enable OFF | ON
26 PT2 Trip threshold Th>2 ^C 0 ... 200 step = 1
Th>2 Operating time
Value s 0 ... 100 step = 1
Th>2 Breaker failure Th>2BF OFF | ON
Th>2 Trip relays Th>2-K K1 | K2 | K3 | K4 | K5 | K6 | K7 | K8 | K9 | K10